The World Leader in Climatic Testing Equipment
 
 
Environmentally Controlled Rooms
Data Sheet (PDF format)  Viewing PDF files requires Adobe Acrobat Reader  
     

Tescor manufactures custom environmental chambers for use in Industrial Testing and Life Science Applications. These chambers can range from walk-in type used for the storage of temperature sensitive pharmaceuticals, to large drive-in chambers used in testing automobiles.

Click the Customize button below to submit your requirements and receive a quotation.

 
Walk-In Environmental Rooms
 

Tescor has utilized its experience in refrigeration and air conditioning technologies to manufacture chambers which can maintain –100°F on a continuous basis or chambers which can reach as high as 250°F. These systems can be supplied with temperature and humidity PID controls or with fully computerized data acquisition and control systems.

Insulation
The room will be constructed of various quantities of standard, pre-molded, modular panels, depending on the size of the room. The insulated panels can be supplied in a wide variety of interior and exterior metal finishes with foamed-in-place urethane insulation. Panels can be supplied in 4" (R-34), 5" (R-42) or 6" (R-50) thickness. Panel edges will have tongue and groove interfaces to assure a tight joint. A flexible vinyl gasket will be fitted on the interior and exterior of each panel along each tongue edge to provide an airtight gasketing at each joint. All panels will lock together from the interior by self-contained cam-lock fasteners. The insulated panels will be UL fire test approved and will have a low flame spread rating of 25 or less. Panels will be tested and approved by Factory Mutual Number 4880, for Class I building type insulated wall and ceiling construction in combination.
 

Conditioning Systems
All operating controls, instrumentation, functional switches and indicator lights will be located at a single control panel center mounted at operator eye level. All operating modes and functions will be clearly indicated by pilot lights and legibly identified by engraved nameplates. The recessed control panel section of the enclosure will be hinged for easy opening by authorized maintenance personnel. Once this panel is swung open and the top section of the control center is removed, all relays, contactors, and other enclosed control circuit devices will be readily exposed for simple maintenance purposes. The control console will be provided with a clear acrylic cover and a lock with 2 keys. Tescor typically provides all solid state, bridge type, proportional, electronic controllers for temperature and humidity control. Automatic reset and rate functions will be incorporated to compensate for error due to load variations. Operating set-points are adjustable and set by means of the pushbuttons on the face of the controller. Both set-point and process variable will be displayed on a large, bright, digital L.E.D. read-out.

 

 
     
TYPICAL SPECIFICATIONS:    
     

Wall Thickness: 4" 5" 6"

Doors:
36" x 78"
48" x 84"
Other:
 

 

 
Windows:
14" x 24"
Other:
 


Floor:
0.080" Textured Aluminum
0.100" Smooth Aluminum
16 Ga. Stainless Steel
14 Ga. Galvanized
 
 

Room Surface Finish: 

Interior:
26 Ga. Galvalume
Embossed Aluminum .032"/.040"
24 Ga. Embossed White Galvanized
0.040 White Embossed Aluminum
Stainless Steel 20 Ga./22 Ga.
 

 
Exterior:
26 Ga. Galvalume
Embossed Aluminum .032"/.040"
24 Ga. Embossed White Galvanized
0.040 White Embossed Aluminum
Stainless Steel 20 Ga./22 Ga.
 
 

 
Condensing Unit Location:  
Room Top Mount
Remote Mechanical Room
Outdoor
 

 
Temperature Range: 
Cold Room:                   +4°C
Freezer Room:              Ambient to -40°C
Incubator Room:            35°C to 60°C
Environmental Room:   0°C to 60°C
Custom Range Room:
 
 


Refrigeration:
Air-Cooled
Water-Cooled
Redundant Systems
 

 
Refrigerants:
R-134a
R-22 or R-407C
R-507 or R-404A
Other Refrigerants Available
 
 


Temperature Control Stability:
± 0.2°C
± 0.5°C
± 1.0°C
 

 
Temperature Uniformity:
± 0.5 °C
± 1.0 °C
 
 


Transition Rates:
Temperature: 0.5° C/minute, average
Humidity: 0.5%/min., non-condensing, avg
Special:
 
 

Humidity Range:
Ambient to 95% RH as limited by 50°C dewpoint
20% to 95% RH as limited by 5°C and 50°C dewpoints
Other
 

 
Recorders: 
One Pen, 10", 7 day, 24 hr per revolution
Two Pen, 10", 7 day, 24 hr per revolution
 
 


Humidity Control Stability:
± 2%

± 5%

   
 


Forced Ventilation: 
15 CFM
50 CFM
75 CFM
Other
 
 

Special Requirements: 

Tescor can design the Environmental Room or Freezer to meet the customer's specific requirements!

Click the Customize button below to submit your requirements and receive a quotation.

Alarms
High/Low Temp Alarms
High/Low Humidity Alarms
Remote Contacts
Power Failure Alarm
Inside "Panic" Alarm 
 
 
 
     